7.2. Non-watertight system: Every disposal system or part of such system that is not watertight must be installed in a place(a) where there is no motorized traffic;
(b) where it is not likely to be submerged;
(c) that is accessible for maintenance; and
(d) that complies with the distances prescribed in the following table:
_______________________________________________________________________________
Reference point Minimum distance
_______________________________________________________________________________
Category 3 groundwater withdrawal facility
referred to in section 51 of the Water
Withdrawal and Protection Regulation
(chapter Q-2, r. 35.2) and uncategorized
groundwater withdrawal facility sealed in 15*
accordance with subparagraphs 1 to 3 of
the first paragraph of section 19 of that
Regulation where sealing took place
between 15 June 2003 and 2 March 2015
or sealed in accordance with section 19 of
that Regulation in other cases.
_______________________________________________________________________________
Other groundwater withdrawal facility and
surface water withdrawal facility 30*
_______________________________________________________________________________
Lake, watercourse, swamp or pond 15*
_______________________________________________________________________________
Dwelling, underground drainage line or drainage trench 5*
_______________________________________________________________________________
Top of an embankment or ditch 3*
_______________________________________________________________________________
Drinking water pipe, property or tree line 2*
_______________________________________________________________________________
* Distance in metres.
The distances referred to in the table in the first paragraph are measured from the end of the disposal system.